Electric Service NOTE:

It is permitted to parallel up to two conductors in the single 350 KCM lug of an S1 pedestal restricted to the following wire sizes: 1/0+1/0 or smaller, 2/0 + # 1 or smaller, 3/0 + # 2 or smaller, 4/0 + # 4 or smaller

Pedestal TypeSingle Run Wire Size RangeParallel Run Max Wire Size
S1# 2 - # 3501/0
S2# 2 - # 350# 350

CT Metering is required for wire size larger than parallel 350.