Electric Service NOTE:
It is permitted to parallel up to two conductors in the single 350 KCM lug of an S1 pedestal restricted to the following wire sizes: 1/0+1/0 or smaller, 2/0 + # 1 or smaller, 3/0 + # 2 or smaller, 4/0 + # 4 or smaller |
||
Pedestal Type | Single Run Wire Size Range | Parallel Run Max Wire Size |
S1 | # 2 - # 350 | 1/0 |
S2 | # 2 - # 350 | # 350 |
CT Metering is required for wire size larger than parallel 350. |